Wrindu

Digital Earth Resistance Tester

The digital earth resistance tester excels in on-site measurements with 3-wire and 2-wire methods. Its unique wire resistance calibration ensures lasting precision, stability, and reliability in diverse environments.
Models: RD3001E, RD3002E

Related Products

Wrindu Handheld PD Tester
double-stage-vacuum-transformer-oilb7e1c
图片
transformer-comprehensive-test-benchf7b9e5a1-76f6-4a19-a072-8aadc4aefb21

OVERVIEW


This digital earth resistance tester is specifically designed for on – site measurement of ground resistance and ground voltage.It can accurately measure ground resistance using 3 – wire and 2 – wire methods, with the help of digital and microprocessing technology. It can judge the resistance of the auxiliary grounding pile and display its resistance value in real – time during the test to prevent errors caused by excessive resistance of the auxiliary grounding electrode and ensure measurement accuracy. It is equipped with a line resistance calibration function to effectively avoid mistakes caused by poor contact of the test line or incomplete insertion of the interface. The test results are stable and reliable even if the test line is replaced or lengthened. It has the functions of automatic shutdown and automatic switching of test gears, strong anti-interference ability, and convenient operation. It is widely used in ground resistance measurement in industries such as electricity, telecommunications, meteorology, oil fields, construction, and lightning protection, and can also accurately measure in complex environments.

 

CHARACTERISTIC

 

  • 1. It is lightweight, portable, easy to carry on – site, simple to operate, and suitable for various measurement scenarios.”
  • 2.During the test, it can display the resistance of the auxiliary grounding pile in real – time, effectively avoiding errors from excessive auxiliary – grounding – electrode resistance and ensuring more accurate measurement results.
  • 3. Equipped with a line resistance calibration function, it can prevent errors caused by poor contact with the test line, making the measurement results more accurate and reliable.
  • 4. Our digital earth resistance tester supports ground voltage measurement, which is convenient for comprehensively evaluating grounding status on site.

 

For more information about ground resistance testers, please click More.
To request the latest quotes, please click Contact Us
.

 

FAQ

 

Q: Why is earth ground testing important?

A: Earth ground testing is vital to mitigate risks linked to insufficient grounding, preventing equipment failure and safety hazards. A robust grounding system establishes a secure pathway for current, which is crucial during events like lightning strikes or overvoltages. This not only safeguards equipment by maintaining stable voltages but also ensures the safety of individuals working with or around electrical infrastructure. Proper earth ground testing is foundational for equipment reliability and personnel safety in diverse electrical scenarios.

 

Q: How can we reduce earth resistance?

A: A longer grounding rod can significantly reduce earthing resistance, especially when it is driven deeper into the ground. This relationship emphasizes the importance of optimal rod length and depth for efficient grounding, ensuring enhanced safety and equipment protection.

 

Q: Is a high earth resistance very good for earthing?

A: No, high earth resistance is not desirable for earthing. Low earth resistance is crucial for effective grounding, as it ensures efficient dissipation of fault currents into the ground, reducing the risk of electric shock and fire hazards. High resistance can lead to increased voltage on exposed metal parts, posing safety risks and compromising the performance of electrical systems.

Technical Parameters

 

Picture Digital Earth Resistance Analyzer Digital Earth Resistance Testing Equipment
Model RD3001E RD3002E
Function Description
Power Supply DC 9V, 6 PCS of R6 AA dry batteries
Display LCD LCD: 58mm×46mm
Tester Dimension 160mm (L) × 100mm (W) × 66mm (H)
Weight Host: about 800g, total weight: about 2285g (including accessories)
Measurement Method Earth resistance: rated current change-pole method, measure current 20mA Max; Voltage to earth: average value rectification
Measurement Time Earth resistance: 15 seconds/time; Voltage to earth: 2 times/second
Overrange Display Overrange overflow function: display “OL” symbol
Auxiliary Ground Rod 2 PCS: Φ10mm×250mm
Test Wires Red 15m, yellow 10m, green 5m, red 1.5m (total 4 pcs wires)
Wire Resistance Verification It can avoid errors caused by poor contact of the test line (such as incomplete insertion into the instrument interface) or when the user replaces or lengthens the test line, ensuring more accurate grounding – resistance measurement.
Auto Shutdown After power is turned on, it will automatically shut down after 3 minutes without any operation.
Battery Voltage When the battery voltage decreases to around 7.2V, the tester will display the low – battery – voltage symbol,and remind you to replace the battery.
Overload Protection Earth resistance: between each interface of E-P, E-C, AC 280V/3 seconds
Data Access Data access function: display “READ” symbol
Electromagnetic Property IEC61010-4-3, wireless frequency electromagnetic field≤1V/m
Safety Standard IEC61010-1, IEC1010-2-31, IEC61557-1, Pollution degree 2, CAT Ⅲ 300V
Working Current Backlight: 56mA Max; Standby: 20mA Max (Backlight close); Measurement: 200mA Max (Backlight close)

 

Measurement Range & Accuracy

 

Model Test Function Range Accuracy Resolution
RD3001E

RD3002E

Earth Resistance 0.01Ω ~ 20Ω ±2% rdg ± 3 dgt

(Auxiliary earth resistance 100Ω±5%, voltage to earth<10V)

0.01Ω
0.1Ω ~ 200Ω 0.1Ω
1Ω ~ 2000Ω
Earth Voltage 0V~200V AC ±2% rdg ± 3 dgt 1V
RD3001E Earth Current 0mA~100A AC ±2% rdg ± 3 dgt 1mA

Related Products

Send Inquiry