Wrindu

SF6 Decomposition Product Tester

The SF6 gas decomposition product tester ensures precise measurements with consistent gas flow through an electrochemical sensor. Incorporating top-notch sensors guarantees accurate and reproducible results.
Models: RDFJ-708A,RDFJ-708B

Related Products

OVERVIEW

 

The SF6 gas decomposition product tester streamlines the process of on-site detection for SF6 decomposition products. Operating seamlessly, it links to a gas chamber housing SF6 gas equipment under pressure. Here, the SF6 gas flows through the electrochemical sensor at a consistent rate, facilitating precise measurements. With its incorporation of top-notch sensors renowned for their reliability and extended lifespan, this device guarantees accurate and reproducible results, ensuring a smooth and efficient testing process from start to finish.

 

CHARACTERISTIC

 

  • Durable detection components for extended lifespan.
  • Enables direct measurement sans coloor sensor.
  • Ensures high accuracy and excellent repeatability.
  • Equipped with built-in pressure regulator and electronic mass flow meter.
  • The SF6 gas decomposition product tester features a large color LCD display for easy reading.
  • Powered by a lithium battery with AC/DC dual functionality.
  • Includes a convenient built-in cleaning function.
Picture

1

1
ModelRDFJ-708ARDFJ-708B
NameTechnical parametersTechnical parameters
Measuring rangeSO2:0 ~ 100μL/L

H2S:0 ~ 100μL/L

CO: 0 ~ 1000μL/L

SO2:0 ~ 100μL/L

H2S:0 ~ 100μL/L

CO: 0 ~ 1000μL/L

HF: 0 ~ 10μL/L

Measuring accuracySO2

When the measured value ≤10μL/L, the error±0.2μL/L

When the measured value≥10μL/L, the error≤±3%

H2S

When the measured value≤10μL/L, the error±0.2μL/L

When the measured value≥10μL/L, the error≤±3%

CO:

When the measured value≤50μL/L, the error±0.5μL/L

When the measured value≥50μL/L, the error≤±4%

SO2

When the measured value ≤10μL/L, the error±0.2μL/L

When the measured value≥10μL/L, the error≤±3%

H2S

When the measured value≤10μL/L, the error±0.2μL/L

When the measured value≥10μL/L, the error≤±3%

CO:

When the measured value≤50μL/L, the error±0.5μL/L

When the measured value≥50μL/L, the error≤±4%

HF:

The error of measured value≤±0.1μL /L

RepeatabilitySO2

When the measured value≤10μL/L,the repeatablity≤±0.1

When the measured value≥10μL/L,the repeatablity≤±2%

H2S

When the measured value≤10μL/L,the repeatablity≤±0.1

When the measured value≥10μL/L,the repeatablity≤±2%

CO:

When the measured value≤50μL/L,the repeatablity±0.3

When the measured value≥50μL/L,the repeatablity≤±3%

SO2

When the measured value≤10μL/L,the repeatablity≤±0.1

When the measured value≥10μL/L,the repeatablity≤±2%

H2S

When the measured value≤10μL/L,the repeatablity≤±0.1

When the measured value≥10μL/L,the repeatablity≤±2%

CO:

When the measured value≤50μL/L,the repeatablity±0.3

When the measured value≥50μL/L,the repeatablity≤±3%

HF:

The repeatability of measured value≤±0.1

Resolution0.1μL/L0.1μL/L
Sampling flow0.2L/min0.2L/min
Measuring time≤180S≤180S
Working environmentTemperature-10℃ ~ +50℃,Humidity0 ~ 90%RHTemperature-10℃ ~ +50℃,Humidity0 ~ 90%RH
Supply powerLithium battery power supply, AC and DC dual-use, automatic switching, overcharge and over-discharge protection functionLithium battery power supply, AC and DC dual-use, automatic switching, overcharge and over-discharge protection function
Dimension330(mm)×220(mm)×150(mm);330(mm)×220(mm)×150(mm);
weight4.6KG4.8KG

Send Inquiry