Wrindu

Load Bank For Battery Discharge Test

To ensure reliability during outages, batteries at power and telecom sites need regular assessment with a load bank for battery discharge tests.
Model: RD-CT Series

Related Products

Wrindu Handheld PD Tester
double-stage-vacuum-transformer-oilb7e1c
图片
transformer-comprehensive-test-benchf7b9e5a1-76f6-4a19-a072-8aadc4aefb21

OVERVIEW

 

In facilities such as power generation stations and telecommunications hubs, batteries are essential for uninterrupted operation during power outages. However, these batteries can suffer a significant reduction in capacity due to various factors, often before their expected lifespan is complete. Therefore, it is crucial to periodically evaluate the condition of these batteries using a load bank for battery discharge test. This reliable method involves a controlled discharge test to accurately measure the battery’s remaining capacity, enabling proactive maintenance and replacement planning.

 

CHARACTERISTIC

 

  • 1. The load bank for the battery discharge test is equipped with a 7-inch LCD touch screen, which makes operation simple and allows for the real-time display of various parameters.

 

  • 2. It offers a choice of discharge modes, including constant current and constant power, to suit different needs.

 

  • 3. The load bank for battery discharge test With 4 adjustable stop points and multiple alarm settings, the discharge process can be intelligently controlled to ensure safety and efficiency.

 

  • 4. Data can be downloaded to a PC via USB, allowing for capacity evaluation and the generation of reports.

 

  • 5. Optional wireless modules are available for real-time measurement of 1.2V/2V/6V/12V cell voltages, with each sensor capable of monitoring 24 cells simultaneously.
Model  RD-CT-24/10 RD-CT -48/15 RD-CT -48/30 RD-CT -110/05 RD-CT -110/10 RD-CT -110/15 RD-CT -220/05 RD-CT -220/10 RD-CT -380/05 RD-CT -380/10
Output voltage 24V 48V 48V 110V 110V 110V 220V 220V 380V 380V
Output current 1-100A 1-150A 1-300A 1-50A 1-100A 1-150A 1-50A 1-100A 1-50A 1-100A
Discharge mode CC, CP
Accuracy & Resolution ≤±0.5%, 0.01V
DC voltage measurement
Internal current range 2-300A
Accuracy & Resolution ≤± 1%; 0.1A
Cell voltage Range 0-15V
Accuracy & Resolution ≤± 0.5%; 0.01 V
AC power supply
Power Supply AC 220V, 50Hz
Cooling mode Air Cooling
Communication & storage
Storage mode SD card and internal storage
Internal memory 16MB flash or optional
Display 7-inch touch screen
High-Voltage insulation test Input-The enclosure: 2200Vdc 1min
Input-Output: 2200Vdc 1min
Output- The enclosure: 700Vdc 1min
Safety standard EN610950
CE Certificate LVD: EN61010-12010; EMC:EN61326-1:2013
Environment
Work temperature -5~50℃
Storage temperature -40~70℃
Humidity 5%~95% RH
Altitude Below 4000 m
Working noise <60 dB
Dimensions of the host machine 55x25x44 mm
Net weight 23 kg